Page 4 - LatitudeCatalog_Hochiki_2021
P. 4
Technical Specifications
2 to 8 LOOP (4 SLOT) ENCLOSURE
Size Standard Cabinet - 420mm (W) x 590mm (H) x 153mm (D)
16.5in (W) x 23.2in (H) x 6in (D)
Deep Cabinet - 420mm (W) x 590mm (H) x 203mm (D)
16.5in (W) x 23.2in (H) x 8in (D)
Construction Mild sheet steel enclosure, 1.5 mm
Cable Entry Knockouts Standard Cabinet - 28 top, 19 back, 1 per side, 2 bottom
Deep Cabinet - 38 top, 19 back, 1 per side, 2 bottom
Optional Semi-Flush Mounting Kit Semi-Flush Mounting Collar Kit
KM5FCRD - Red
KM5FCGY - Gray
KM5FCBS - Black
Battery Capacity Standard Cabinet - Up to 28 Ah (Power Sonic PS-12280)
Deep Cabinet - Up to 40 Ah (Power Sonic PS-12400)
2 to 16 LOOP (8 SLOT) ENCLOSURE
Size Standard Cabinet - 540mm (W) x 720mm (H) x 160mm (D)
21.3in (W) x 28.3in (H) x 6.3in (D)
Deep Cabinet - 540mm (W) x 720mm (H) x 212mm (D)
21.3in (W) x 28.3in (H) x 8.3in (D)
Construction Mild sheet steel enclosure, 1.5 mm
Cable Entry Knockouts Standard Cabinet - 38 top, 25 back, 2 per side, 2 bottom
Deep Cabinet - 50 top, 25 back, 2 per side, 2 bottom
Battery Capacity Standard Cabinet - Up to 28 Ah (Power Sonic PS-12280)
Deep Cabinet - Up to 40 Ah (Power Sonic PS-12400)
ALL MODELS
Finish Epoxy powder coated
Color Lid & Box Red (RAL3002) Gray (BS 00 A 05) Black (RAL9005)
Fascia Signal White (RAL9003)
Power supply voltage 120 V AC or 240 V AC
Power supply rating at 24V DC 5.25 A (charges up to 60 Ah)
10.25 A (charges up to 100 Ah)
Display Full-color 800 x 480 LCD with resistive touch screen and automatic backlight dimming.
Software zones 2000
Software groups 5000
Cause and Effects 5000
Event log 10,000 events, 1 second resolution. Filterable and printable.
Detection loops 2 - 16, added 2 at a time via dual loop panel module (S758)
Detection loop current 400 mA each
AUX 24V Output 2; each rated at 900 mA
NACs 4; each rated at 2.5 A. Max 5A combined output for all channels. Class B or 2 Class A.
Programmable Relay Outputs 5; 30 V DC 1 Amp
Programmable Inputs 3; designed to be activated by voltage-free contacts
Network Connection Optional network card provides communication for networking fire control panels
NAC Synchronization Internal Support of System Sensor, Wheelock, Gentex, and Amseco protocols
Printer (OPTIONAL) 40 column, front-loading thermal
Zone LED Indicators (OPTIONAL) Up to 3 banks of 48 (144) as standard
4 FireNET L@titude Product Guide, v. 2.0